VEGA

Double conversion on-line UPS with output transformer, from 10 to 100KVA with SCR rectifier.

Caratteristiche

Uninterruptible power systems with single phase output for industry equipment, security systems, industrial processes, critical infrastructures, electromedical equipment, monolithic protection of power supply in datacenters.

  • Heavy design and high reliability.
  • Solutions in parallel up to 2 MVA.
  • Optimized configurations for industrial applications.
  • Customizations for special process applications.


  • Space optimization: optimized design of the internal components and cooling system
  • Low operating costs and high efficiency
  • Total-controlled SCR rectifier, proven technology for maximum reliability
  • Minimum maintenance requirements: front access to components and the high quality of the materials used minimize maintenance costs.
  • External battery monitoring system (BMS) for the specific monitoring of the battery (optional)



  • Double conversion online UPS, classified as VFI-SS-111 according to the product specification IEC EN 62040-3.
  • Integrated inverter output transformer for galvanic isolation
  • Hot-parallelizability for easy expansion of the system.
  • Total-controlled SCR rectifier, proven technology for maximum reliability.
  • Battery protection
  • Configurations in power parallel or redundant with distributed or centralized static bypass to manage large short-circuit currents.
  • Parallel control based on CAN-bus for load distribution accuracy
  • Full range of monitoring solutions for complete control of the system functionality.
  • Full compliance with international IEC standards




 

More info?

Contact us!

Applications

  • Small and medium-sized data centers
  • Network & Server
  • Industrial controls and process automation
  • CNC machines
  • Medical equipment
  • Building automation
  • Safety and emergency systems


Category: Tag:

Description

DATA SHEET

 

MODELS

VM10

VM15

VM20

VM30

VM40

VM60

VM80

VM100

INPUT
Rated Voltage 380 – 400 – 415 Vac 3Ph
Voltage tolerance 400 V + 20% /- 25%
Frequency 45 – 65 Hz
Soft start 0 – 100% in 120’’ (selectable)
Frequency tolerance permissible ± 2% (selectable da ± 1% a ± 5% da front panel)
Standard amenities Protection di Back Feed; linea di bypass divisible
BYPASS
Rated voltage 220 – 230 – 240 Vac single phase + N
Rated frequency 50 or 60 Hz (selectable)
OUTPUT
Rated power (kVA) 10 15 20 30 40 60 80 100
Active power (kW) 9 13,5 18 27 36 54 72 90
Number of phases 1
Rated voltage 220 – 230 – 240 Vac single phase + N (selectable)
Static stability ± 1%
Dinamic stability ± 5% in 10 ms
Voltage distortion < 1% con linear load / < 3% with distortion load
Crest Factor 3:1 lpeack/lrms
Stability frequency on battery 0,05%
Frequency 50 or 60 Hz(selectable)
Overload 110% for 60’; 125% for 10’; 150% for 1’
BATTERY
Type VRLA AGM / GEL; NiCd; Supercaps; Li-ion; Flywheels
Ripple < 1%
Temperature compensation -0,5 Vx°C
Charge current typical 0,2 x C10
INSTALLATION INFO
Weight without batteries (kg) 200 220 230 270 302 440 500 580
Dimensions (LxDxH) (mm) 555x740x1400 800x740x1400 800x800x1900
Remote signals SPDT contacts
Remote commands ESD e bypass
Communication RS232 double + clean contacts + 2 slot for communication interface
Ambient temperature 0 °C/ +40 °C
Relative humidity <95% not condensed
Colour dark gray RAL 7016
Noise at 1 m (ECO Mode) 60 dBA 62 dBA
Protection degree IP20
Efficiency Smart Active fino a 98%
Regulations Direttive LV 2006/95/EC – 2004/108/EC; Security IEC EN 62040-1;
EMC IEC EN 62040-2; Prestazioni IEC EN 62040-3
Classification by IEC
62040-3
(Voltage Frequency Independent) VFI – SS – 111
Moving the UPS UPS Transpallet

Additional information

Sottotitolo

Double conversion on-line UPS

Testo breve

with output transformer, 10 to 80KVA with SCR rectifier

Reviews

There are no reviews yet.

Be the first to review “VEGA”